ABOUT THE TRANSDUCER
The Echomax XPS / XCT series of transducers
operates in association with Milltronics ultrasonic
level monitoring products.
The transducer converts the electrical energy of the
transmit pulse from the transceiver into acoustical
energy. It then converts the acoustical energy of
the echo back into electrical energy for the
transceiver receive period.
The effective acoustical energy is emitted from
the transducer face and radiated outward,
decreasing in amplitude at a rate inversely
proportional to the square of the distance.
Maximum power is radiated axially (perpendicular)
from the transducer face in a line referred to as
the axis of transmission. Where power is reduced
by half (– 3 dB), a conical boundary defining the
sound beam, centered about the axis of transmission,
is established. The diametric measurement of the cone in degrees defines the beam angle.
Impedance matching techniques are used to optimize the transfer of power from the
transducer into air and vice versa.
The XPS / XCT transducers incorporate an integral temperature sensor that reports the air
temperature at the transducer to the transceiver. The connection is transparent, in that both
the ultrasonic and temperature components of the transducer use the same leads.
GENERAL GUIDELINES
This equipment may be used in all hazardous zones and with all gases with temperature
classes T1, T2, T3 and T4 for the XPS series (XPS-10, XPS-15, XPS-30 and XPS-40) and T1,
T2 and T3 for the XCT series (XCT-8 and XCT-12). The XPS series is only certified for use in
ambient temperatures in the range of - 40°C to 95°C and the XCT series is only certified for
use in ambient temperatures in the range of -40°C to 145°C. Neither should be used outside
of their respective temperature ranges.
Installation shall be carried out in accordance with the applicable code of practice, and by
suitably trained personnel.
These devices should only be supplied from a circuit containing a suitably-rated fuse that has
a breaking capacity of 4000A. This fuse in included in Milltronics’ transceivers.
Repair of this equipment shall be carried out in accordance with the applicable code of
practice.
The certification of this equipment relies on the following materials used in their construction:
Material XPS Series XCT Series
Enclosure Kynar 710 Kynar 710
Encapsulant LA-9823-76 Durapot 861-F3 & 864
Manual override can be accomplished by using the disconnect switch provided in the building
installation of the associated controller.
transducer
transducer face
– 3 db
boundary
axis of
transmission,
perpendicular to
transducer face
PL-521 3