WIRING FORMATS (cont’d)
BIC-II / AiRanger XPL Plus Interconnection
1. BIC-II, ports 1-6, Rx input is non-polarized.
2. Refer to instruction manual PL-400 for wiring of AiRanger XPL Plus.
Check that Peripheral Communications (P-740) is set for "normal".
3. BIC-II interconnecting cable shield should be connected at AiRanger XPL Plus only. Insulate shields
at junctions to prevent inadvertent grounding. Use Belden cable 8760, 1 pair shielded / twisted,
18 AWG or equivalent. Maximum communication loop length is 3000 m ( 10,000 ft ).
4. All wiring, whether in non-hazardous (as shown) or hazardous areas, must be done in conjunction with
approved conduit, boxes and fittings, and to procedures in accordance with all governing regulations.
5. Set BIC-II and AiRanger XPL Plus voltage selection jumpers for proper voltage supply.
Supply voltages higher than voltage selected will severely damage unit.
FIG. 3H
96/01/09
BIC-II
AiRanger XPL Plus #1
(Board B)
to other products
as required
communication
loop
PL-371 12 – 10